RZ2SCY

The RZ2CY sub-C cell delivers non-flammable safety, high-power density, and rapid production scalability in an adaptable cylindrical format. Designed for multiple module configurations, it provides a flexible foundation for data center UPS cabinets, auxiliary DC systems, and distributed backup power applications where safety, power, and scale must come together.
Type
Critical Power Rechargeable Nickel-Zinc Cylindrical Cell
Nominal Dimension (with Case)
Diameter = 23.0mm
Height = 43.0mm
Applications
Recommended discharge current 400mA to 20000mA
Nominal Voltage
1.65V
Capacity
Rated: 2000mAh
Minimum: 1900mAh
When discharged at 400mA to 1.3V at 25°C
Available Energy (Beginning of Life)
3.2Wh
Max. Continuous Discharge Current
40A (100% Depth of Discharge)
Continuous Charge Current
1000 – 2000mA
Max. Charging Voltage
1.9V
Recommended Float
1.85 – 1.9V
Charge Time @max rate
60 minutes@1C
Standard Charging Condition
Two Step Charging
Constant Current: 1000mA CC to 1.9V
Constant Voltage: 1.9V CV to 200mA cut off
Weight
~46g
Internal Resistance
Less than 6mΩ upon fully charged at 1000Hz
Ambient Temperature Range
Standard Charging: 0 to +40°C
Fast Charging: +10°C to +40°C
Discharging: -30°C to +80°C
Storage: -20°C to +35°C
Storage (1 week): -20°C to +60°C
Typical 3W Constant Power Discharge
Typical 3W Constant Power Discharge at +25ºC
Typical 3W Constant Current Discharge at +25ºC
End Voltage
1V
Up to 2 mins.
60
3 mins.
47
5 mins.
47
10 mins.
17
20 mins.
9
30 mins.
6
45 mins.
4
60 mins.
3
End Voltage
1.25V
1V
Up to 2 mins.
41.7
50
3 mins.
33
36
5 mins.
21.4
22
10 mins.
10.9
11
20 mins.
6
6
30 mins.
7
7
45 mins.
2.5
2.5
60 mins.
2
2
RZ7V32

The RZ7V32 pack is a scalable, high-power building block for data center backup, from battery cabinet to full system. Built with inherently safe, non-flammable sub-C cells, it delivers the power, flexibility, deployment speed, and more sustainable chemistry needed for critical infrastructure where uptime, safety, and scalability are essential.
Type
Critical Power Rechargeable Nickel-Zinc Pack
Nominal Voltage
6.6V
Capacity
Rated: 58Ah
Nominal Energy
3.4kWh
Maximum Discharge Current
700A
Standard Charging Method
Two Step Charging Constant Current: 32A CC to 7.6V
Constant Voltage: 7.6V CV to 5.8A cut-off TCV = -0.0032T+7.68V
Charge Cut-off Voltage
7.6V
Standard Charge Current
32A
Maximum Charge Current
64A
Discharge Cut-off Voltage
80V
Operating Temperature Range
-30℃ to +80℃
+20℃ to +35℃ (optimum)
Storage Temperature Range
-20℃ to +35℃
Humidity Range
0 - 90%, Non-condensing
Safety
Batteries exhibit no thermal runaway as per UL9540A
Transport
No Transportation Restrictions
Dimensions (mm)
203(w) x 193(d) x 116(h)
Weight
6.9kgs
Battery (cell level)
IEC62133-1, EU Battery Directive (2011/65/EU)
Standard 0.5C Charge at +25℃

Typical Constant Power Discharge at +25℃

RZ110V

The RZ110V DC Auxiliary Cabinet is a next-generation smart battery solution that keeps critical switchgear, controls, and auxiliary DC systems energized.
Key Features
Next Generation Chemistry
Smaller Footprint
Highly Recyclability
Smart Battery Controls
Non-Flammable
Cadmium-Free
The integrated HMI provides operators with real-time visibility into cabinet status, battery health, alarms, and operating data. Through standard communication and I/O interfaces, the system can interface with UPS and other power infrastructure equipment, supporting streamlined monitoring, diagnostics, and control within data centre environments.
MODEL
RZ110V
Electrical
Function
DC Auxiliary Cabinet
Nominal Voltage
105.6V
Charge Cut-off Voltage
121.6V
Standard Charge Current
20A
Maximum Charge Current
40A
Discharge Cut-off Voltage
80V
Nominal Capacity
32Ah
Nominal Energy
3.4kWh
Maximum Discharge Current
100A
Battery Chemistry
Nickel-Zinc (Alkaline Electrolyte)
System BMS Functions
Monitoring
Modbus RTU / Dry Contact /Modbus TCP
Power Supply
120/230VAC 50/60Hz standard, with 110V DC redundant
Data Communications
RS485 standard configuration
Safety and Environment
Safety
Batteries exhibit no thermal runaway as per UL9540A
Breaker Protection
Manual or upon fault
Operating Temperature Range
-30℃ to +80
+20℃ to +35℃ (optimum)
Storage Temperature Range
-20℃ to +35℃
Humidity Range
0 - 90%, Non-condensing
Cooling
Passive coolant
Transport
No Transportation Restrictions
Mechanical
Dimensions (mm)
800(w) x 650(d) x 1400(h)
Weight
205kgs
Certifications
Battery
IEC62133-1, EU Battery Directive (2011/65/EU)
RZ594V

The RZ594V UPS cabinet is a modular power backup solution with the capability for fast charging to ensure uptime in roles supporting data centers and related critical infrastructure.
Key Features
Superior Safety Performance
High-Power Density
Modular & Scalable Design
Resilient BMS Integration
High Efficiency. Lower PUE
Sustainable Solution

MODEL
RZ59V32
RZ594V
Electrical
Function
BMU
UPS Cabinet
Nominal Voltage
59.4V
594V
Charge Cut-off Voltage
68.4V
684V
Standard Charge Current
30.4A
30.4A
Maximum Charge Current
60.8A
60.8A
Discharge Cut-off Voltage
450V
450V
Nominal Capacity
60.8Ah
60.8Ah
Nominal Energy
3.6kWh
36.1kWh
Maximum Discharge Current
800A
800A
Battery Chemistry
Nickel-Zinc (Alkaline Electrolyte)
Maximum Parallel
10 BMU
16 Cabinets
System BMS Functions
Monitoring
via cabinet
Modbus RTU / SNMP / Modbus TCP
Power Supply
Supplied by cabinet
120/230VAC 50/60Hz standard, with 600VDC redundant
Data Communications
CAN communication
RS485 standard configuration
Safety and Environment
Safety
Batteries exhibit no thermal runaway as per UL9540A
Breaker Protection
N/A
Manual or upon fault
Operating Temperature Range
-30℃ to +80℃
+20℃ to +35℃ (optimum)
Storage Temperature Rang
-20℃ to +35℃
Humidity Range
0 - 90%, Non-condensing
Cooling
Forced ventilation via 2 fans/BMU
Transport
No Transportation Restrictions
Mechanical
Dimensions (mm)
695(w) x 685(d) x 138(h)
800(w) x 800(d) x 2000(h)
Weight
70kgs
960kgs
Certifications
Battery
IEC62133-1, EU Battery Directive (2011/65/EU)
Seismic
N/A
Level 9 (CN:YD5083)
Charging Limit Voltage
© GP Energy Tech. All rights reserved.